  • #1

We bought a new heater this season, a Raypak 206,000 BTU NG Electric Heater RHM-15-9962. It heated the pool nicely earlier in the week, but we turned it off when a cool spell was forecast. This morning I tried to turn it on and I get this error message: "Rollout SW Open". What does this mean? I appreciate the help.

JasonLion

0

TFP Expert

Platinum Supporter

LifeTime Supporter

May 7, 2007
37,770
Silver Spring, MD
  • May 18, 2013
  • Add bookmark
  • #2

Here is what I found in the manual: Roll Out Sw Open - Rollout Switch - verify gas pressure, combustion air, blocked heat exchanger, proper vent size/connections, high wind conditions.

ps0303

0

TFP Expert

In The Industry

Jul 6, 2011
4,177
FL
  • May 19, 2013
  • Add bookmark
  • #3

The rollout switch is activated when something like wind causes the flames to shoot out towards the front of the unit. This is usually caused by high winds while the unit is running. Are you sure it it said rollout? Sounds odd that you turn it on and the switch is open.

The rollout switch connects inside the cabinet right behind where the gas pipe comes into the gas valve. I have seen a few cases where the installer moved the rollout switch so they could install the gas pipe and they failed to put it back in place. This dangling switch is right by the burners then and when the units lights, its possible for the switch to trip open.

In any case this unit is under warranty. Hopefully your installer is also a warranty person for Raypak. Call them and have them come back and look at why the switch failed.

tlwilson

0

LifeTime Supporter

Aug 15, 2010
50
Nebraska
  • May 19, 2013
  • Add bookmark
  • #4

Thank you for your reply. It definitely says "Rollout SW Open". I will call the installer for the repair.

tlwilson

0

LifeTime Supporter

Aug 15, 2010
50
Nebraska
  • Jun 14, 2013
  • Add bookmark
  • #5

Our heater is still not fixed. They determined it wasn't getting enough gas so the gas company replaced our meter. Turned it on and the same thing happened. Now they say the wind diminished the flame and did something to the fireman's switch. Fireman's switch replaced and the wind keeps blowing out or diminishing the flame. Back and forth on how to protect it from the wind. Anybody with advice?

ps0303

0

TFP Expert

In The Industry

Jul 6, 2011
4,177
FL
  • Jun 15, 2013
  • Add bookmark
  • #6

The only thing you can do is add a wind stack to it. You've never had this issue before wind?

tlwilson

0

LifeTime Supporter

Aug 15, 2010
50
Nebraska
  • Jun 15, 2013
  • Add bookmark
  • #7

Our previous heater never had this problem. It was old and inefficient (still worked), but we wanted to upgrade. Raypak heater "Rollout SW Open" (8)

ps0303

0

TFP Expert

In The Industry

Jul 6, 2011
4,177
FL
  • Jun 15, 2013
  • Add bookmark
  • #8

Add the Raypak high wind stack. Probably $100 or around there.

tlwilson

0

LifeTime Supporter

Aug 15, 2010
50
Nebraska
  • Jun 15, 2013
  • Add bookmark
  • #9

Thanks for the help. I appreciate it!

B

[emailprotected]

0
Aug 26, 2014
1
Pensacola Florida
  • Aug 26, 2014
  • Add bookmark
  • #10

How did you solve the problem

Enjoying this content?

Support TFP with a donation.

Give Support

Jun 6, 2013
898
IL
  • Aug 26, 2014
  • Add bookmark
  • #11

I wonder if you have a bad roll out switch. My old RP2100 heater had a wax one and I replaced it with a solid state one. It had a red reset button on it. That solved my roll out problem at the time. They also sell roll out switches that have different shutoff temps by about 10-15deg if I remember but you may not want to go there. I did buy one of the solid state versions which was higher but didn't need it.

J

Jayryght

0
Aug 19, 2016
11
Toronto, Canada
  • Aug 19, 2016
  • Add bookmark
  • #12

I have the same problem. Just happened to me today. I bought and got my heater installed in October 2013 and it heated the pool really nicely. I haven't used the heater in about a week. It's been really hot in Toronto. Today I wanted to do an evening swim with the kids and my wife so I thought I'd turn it on and had the "Rollout SW Opem" message. I thought it was a glitch so I cut the power to the unit and turned it back on, cut the gas and turned it back on, opened up the panel and cleaned any debris I could with a cloth rag and nothing. After reading the comments here I have located the switch but it does not have a reset button. I read somewhere that the newer models do not have one. Is it time to call for service or is there anything else I can do on my end? RSVP

Pool Clown

In The Industry

Sep 5, 2008
2,186
Silicon Valley, CA
  • Aug 20, 2016
  • Add bookmark
  • #13

If it is a Raypak heater, the roll out sensor is a one time use part, like a fuse, it isnt re-settable. I would replace it, leave the front cover removed, start the heater, and observe if the flame "rolls out". If you see this happen, turn off the heater immediately, and have a tech check the exchanger for sooting.

J

Jayryght

0
Aug 19, 2016
11
Toronto, Canada
  • Aug 20, 2016
  • Add bookmark
  • #14

Pool Clown said:

If it is a Raypak heater, the roll out sensor is a one time use part, like a fuse, it isnt re-settable. I would replace it, leave the front cover removed, start the heater, and observe if the flame "rolls out". If you see this happen, turn off the heater immediately, and have a tech check the exchanger for sooting.

I tried that. It doesn't even ignite. Nothing happens. It is just the error message.

wjr75

0

LifeTime Supporter

Jun 6, 2013
898
IL
  • Aug 20, 2016
  • Add bookmark
  • #15

You can jumper across the roll out sensor to see if it starts. This is just for testing purposes and shouldn't be left that way. Might have blown the replaced sensor again or may have some other board issue.

Pool Clown

In The Industry

Sep 5, 2008
2,186
Silicon Valley, CA
  • Aug 20, 2016
  • Add bookmark
  • #16

Jayryght said:

I tried that. It doesn't even ignite. Nothing happens. It is just the error message.

Did you replace the roll out sensor?
Trace the roll out sensors' wires all the way back to the board to make sure they haven't been chewed on.

J

Jayryght

0
Aug 19, 2016
11
Toronto, Canada
  • Aug 20, 2016
  • Add bookmark
  • #17

Re: Raypak heater "Rollout SW Open"

@wjr75 How do I do that? "Jumper across the rollout sensor?"

- - - Updated - - -

@pool clown: no I did not replace it. Not sure how to do that? I see the wires tracing up towards panel, but I guess I have to take off the panel to see it's source right?

- - - Updated - - -

@pool clown: no I did not replace it. Not sure how to do that? I see the wires tracing up towards panel, but I guess I have to take off the panel to see it's source right?

wjr75

0

LifeTime Supporter

Jun 6, 2013
898
IL
  • Aug 20, 2016
  • Add bookmark
  • #18

To jumper across you need a wire across the two terminals where the fuse (roll out sensor) is plugged into. If you do any electrical testing you usually have an alligator clip jumper wire which has one on both ends. But as said before this would be temporary.

J

Jayryght

0
Aug 19, 2016
11
Toronto, Canada
  • Aug 21, 2016
  • Add bookmark
  • #19

@wjr75 Thanks for the tip but I know verrrry little about electrical work and I don't even know what an alligator clip jumper wire is. At this point I may bite the bullet and call a tech. Kudos for your help though.

ps0303

0

TFP Expert

In The Industry

Jul 6, 2011
4,177
FL
  • Aug 22, 2016
  • Add bookmark
  • #20

Yes if you don't know much about electric or gas, call a tech and have them check it out.

Enjoying this content?

Support TFP with a donation.

Give Support

You must log in or register to reply here.

Raypak heater "Rollout SW Open" (2024)

FAQs

What does SW open mean on Raypak pool heater? ›

The sw water error is telling you the flow of water through the heater is not sufficient to start the heater. This is typically due to a dirty filter. If a sand filter backwash. If a cartridge or de filter remove and clean.

How do you troubleshoot a Raypak pool heater? ›

Go make sure there aren't any tripped circuit breakers in the fuse box, then check that the unit's time clock is set to the “On” position. Check Filters & Strainers: Problems with slow or inefficient heating, as well as overly noisy operation, can sometimes be traced back to dirty filters and strainers.

What causes a rollout switch to open? ›

The flame rollout sensor will only trip if the furnace has an underlying problem, such as blocked vents, overheating, or gas pressure issues. Ensure that you don't opt to keep resetting the switch and keeping the furnace running.

How long should a Raypak pool heater last? ›

The average life of a pool heater is between 15 and 25 years with regular usage and proper maintenance, but there are various factors that impact that projection. To make your pool heat pump last as long as possible, stick to proper usage and emphasize maintaining the system.

Why does my Raypak pool heater keep shutting off? ›

If one day you wake up and your pool heat pump stops running, the first thing to check is your water flow. Without an adequate source of water, a pool heat pump automatically shuts down to prevent overheating. This is sometimes the cause of what many describe as a pool heat pump turning off and on.

What is the purpose of a rollout switch? ›

The flame rollout switch is a safety feature that shuts off the gas supply to the burner if the flame blows out. This can happen for several reasons, such as a dirty burner or a blocked flue. A flame rollout can also be caused by a faulty gas valve or a problem with the electrical igniter.

Why does my pool heater spark but not light? ›

Check the Pilot Light

If there is no spark, you may need to replace your ignition control (you can test it first with a voltmeter to see if it has enough voltage). If you see a spark but the pilot still does not light, you may have a faulty gas valve, clogged pilot assembly, or poor ventilation.

What does SW open mean on a pool heater? ›

Pool and Spa Expert: garrygoeson. garrygoeson : When your heater is displaying "Water Switch Open", it does not always require the pressure switch to be adjusted.My first suggestion is to thoroughly clean the filter, and make certain the pump basket and skimmer basket is clean of any leaves or debris.

How do you know if your pool heater is bad? ›

Top 6 Signs Your Pool Heater Needs to be Repaired
  • Inconsistent Heating. One of the most obvious signs that your pool heater requires attention is inconsistent water temperature. ...
  • Unusual Noises. ...
  • Reduced Water Flow. ...
  • Visible Leaks. ...
  • Rust or Corrosion. ...
  • Keeps Shutting Off.
Jan 11, 2024

Why is my pool heater not blowing hot air? ›

It could also be that your pool filter is clogged or broken, the filter valve is not open, or the temperature of your heater is not set properly. If the issue is that your pilot won't light, then it could be low gas pressure, poor air supply, or improper venting.

What does roll out switch mean? ›

The flame rollout switch is a safety feature that shuts off the gas supply to the burner if the flame blows out. This can happen for several reasons, such as a dirty burner or a blocked flue. A flame rollout can also be caused by a faulty gas valve or a problem with the electrical igniter.

Is the flame rollout switch normally open or closed? ›

The flame rollout switch is normally closed and opens on high temperature from the flame. The switch is meant to open if the flame is pushed backward away from the heat exchanger area where the flame should be traveling toward. When the switch opens, the control board stops sending power to the electrical gas valve.

Top Articles
Manus, Father of the Abyss
Dark Souls: How To Complete Chasm of The Abyss & Defeat Manus
Hotels Near 625 Smith Avenue Nashville Tn 37203
Windcrest Little League Baseball
Mopaga Game
Wmu Course Offerings
Kansas Craigslist Free Stuff
Songkick Detroit
Pickswise the Free Sports Handicapping Service 2023
Best Restaurants In Seaside Heights Nj
Tcu Jaggaer
Notisabelrenu
Valentina Gonzalez Leak
Colts seventh rotation of thin secondary raises concerns on roster evaluation
Accuradio Unblocked
Craigslist Pets Athens Ohio
House Party 2023 Showtimes Near Marcus North Shore Cinema
Byte Delta Dental
Payment and Ticket Options | Greyhound
Does Breckie Hill Have An Only Fans – Repeat Replay
Driving Directions To Bed Bath & Beyond
Aldine Isd Pay Scale 23-24
Ukc Message Board
Arre St Wv Srj
Sizewise Stat Login
At&T Outage Today 2022 Map
Znamy dalsze plany Magdaleny Fręch. Nie będzie nawet chwili przerwy
When His Eyes Opened Chapter 3123
Bayard Martensen
Shiny Flower Belinda
Penn State Service Management
Cvs Sport Physicals
Bj's Tires Near Me
Salemhex ticket show3
ATM, 3813 N Woodlawn Blvd, Wichita, KS 67220, US - MapQuest
DIY Building Plans for a Picnic Table
Redding Activity Partners
L'alternativa - co*cktail Bar On The Pier
Clearvue Eye Care Nyc
2012 Street Glide Blue Book Value
Greater Keene Men's Softball
Mandy Rose - WWE News, Rumors, & Updates
Conroe Isd Sign In
Ucsc Sip 2023 College Confidential
Vindy.com Obituaries
Youravon Com Mi Cuenta
Www Pig11 Net
Costner-Maloy Funeral Home Obituaries
Strawberry Lake Nd Cabins For Sale
Dumb Money Showtimes Near Regal Stonecrest At Piper Glen
Philasd Zimbra
Honeybee: Classification, Morphology, Types, and Lifecycle
Latest Posts
Article information

Author: Duane Harber

Last Updated:

Views: 5352

Rating: 4 / 5 (71 voted)

Reviews: 86% of readers found this page helpful

Author information

Name: Duane Harber

Birthday: 1999-10-17

Address: Apt. 404 9899 Magnolia Roads, Port Royceville, ID 78186

Phone: +186911129794335

Job: Human Hospitality Planner

Hobby: Listening to music, Orienteering, Knapping, Dance, Mountain biking, Fishing, Pottery

Introduction: My name is Duane Harber, I am a modern, clever, handsome, fair, agreeable, inexpensive, beautiful person who loves writing and wants to share my knowledge and understanding with you.